Replace estimated COP with calorimetric COP for Sevra Split 8kW
Old formula: COP = 5.0 - (T1-T4)*0.05 (rough estimate, not a measurement) New formula: COP = (flow_lh × 1.163 × (TW_out - TW_in)) / P_el Where: - flow_lh = water_flow_register × 22.1 L/h (derived from Sevra 8kW nominal 1370 L/h) - TW_in/TW_out from RS485 registers - P_el = outdoor_unit_current × outdoor_unit_voltage Also added sensor.moc_cieplna_pompy [W] for thermal power output. Note: SCOP from power_output_lo register is NOT thermal COP - it measures compressor shaft power ratio, not heat output. Left as-is with comment. Current result: COP=5.42 at T4=6°C, TW_in=27, TW_out=31, freq=57Hz (plausible) Co-authored-by: Copilot <223556219+Copilot@users.noreply.github.com> |
|---|
|
|
| ha-configs/151/configuration.yaml |
|---|